DSE Model 5110 Automatic Start Engine Management Instrumentation System
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006
27
CONFIGURABLE OUTPUTS (CONTINUED)
Factory default settings are in
bold italicised
text.
Parameter Selection
28 – Output 3 0 - Unused
1 - Preheat mode 0
2 - Air flap
3 - Load transfer
4 - Energise to stop
5 - Engine running
6 - Shutdown alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Auxiliary input 3 active
11 - Auxiliary input 4 active
12 - Auxiliary input 5 active
13 - Preheat mode 1
14 - Preheat mode 2
15 - Preheat mode 3
16 - Warning alarm
17 - Common alarm
NOTE:- The ‘preheat modes’ selectable for configurable outputs and LCD indicators perform the following actions :
•
Preheat mode 0 - Preheat during preheat timer, ceasing at end of preheat timer.
•
Preheat mode 1 - Preheat during preheat timer and continue until engine stops cranking.
•
Preheat mode 2 - Preheat during preheat timer and continue until the safety delay timer has expired.
•
Preheat mode 3 - Preheat during preheat timer and continue until the warming timer has expired.
In addition, in all preheat modes, preheat takes place during the crank rest timer between crank cycles.