DSE Model 5110 Automatic Start Engine Management Instrumentation System
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006
51
18.8 FRONT PANEL CONFIGURATION MK2 5110 V3
TIMERS & ANALOGUE SETTINGS
NOTE:- Setting a timer to zero (0) will disable it. Timer settings increment from 0 to 60s in steps of 1s and from 1
minute to the maximum value in steps of 30 seconds (0.5 minutes) (where applicable)
NOTE:- Setting Flywheel teeth to zero (0) will disable magnetic pickup speed sensing. In this instance, engine speed
is derived from the alternator output frequency.
NOTE:- CT values increment from 10-100 in steps of 10A, and from 100 to 6000A in steps of 50A. CT secondary must
be 5A.
Parameter
Type
Default
Max
0 - Start delay
Timer
5s
60s
1 - Preheat
Timer
0s
60s
2 - Crank attempt
Timer
10s
60s
3 - Crank rest
Timer
10s
60s
4 - Safety delay
Timer
8s
60s
5 - Warming up
Timer
0s
60m
6 - Return delay
Timer
30s
60m
7 - Cooling run
Timer
60s
60m
8 - E.T.S. solenoid hold
Timer
0s
60s
9 - Sensor fail delay
Timer
2s
5s
10 - Fail to Stop Delay
Timer
60s
60s
11 - Low Oil Pressure
Trip
15PSI
150PSI
12 - High Temperature
Trip
95°C
150°C
13 - Under Speed
Trip
1250RPM
3600RPM
14 - Over Speed
Trip
1750RPM
5000RPM
15 - Underfrequency
Trip
40Hz
60Hz
16 - Overfrequency
Trip
57Hz
72Hz
17 - Charge Alt Failure
Warning
8V DC
25V DC
18 - Flywheel teeth
Value
0
300
19 - CT Primary
Value
500A
6000A
Parameter
Selections
20 - Alternator poles
0,2,
4
,6,8
21 – Fast loading enabled
0
,1
22 - AC system
0 - 3 phases 4 wire
1 - Single phase 2 wire
2 - 3 phases 3 wire
3 - 2 phases 3 wires
23 - Oil pressure display units
0 - Bar/PSI
1 - kPa
NOTE:- This section details the configuration editor of the “V3” 5110 module. To identify the “original” and “new” (V2
onwards) controllers, See the section entitled Identification of “original” 5110 and “new” 5110 elsewhere in this manual.
ACCESSING THE CONFIGURATION EDITOR
Press the Stop/Reset
and Info
buttons
simultaneously.
•
The LED beside the AUTO button will
flash continuously to indicate that
configuration mode has been entered.
•
The first configuration
setting is displayed:
From the configuration table, this example is
displaying
Start Delay
(parameter 0). It is currently
set to
5 seconds
.
(Factory default settings are shown in the
configuration table in
bold italic
text)
EDITING A PARAMETER
•
Enter the editor as described above.
•
Press
+
/
-
to scroll through the parameters to
the one you want to change.
•
Press
9
to enter edit
mode. The
symbol
will flash on the display
to indicate that edit
mode has been entered.
•
Press
+
/
-
to change the parameter to the
desired value.
•
Press
9
to save the value and exit edit mode for
this parameter.
•
The
symbol will be removed from the display
to indicate that edit mode has been exited.
•
To select another value to edit, press the
+
/
-
buttons. Continuing to press the
+
and
–
buttons
will cycle through the adjustable parameters as
shown in the following lists.
NOTE:- This page contains configuration details for the “new” V3 5110 only ! For details of the “new”(V4) 5110 and
“original” 5110 see the Front Panel configuration section elsewhere in this manual