6.23. Errors
Function
The device measures the following error conditions.
Sequence of operations
Error
number:
Explanation:
1
L1 voltage dip
2
L2 voltage dip
3
L3 voltage dip
4
L1 voltage interrupt
5
L2 voltage interrupt
6
L3 voltage interrupt
7
L1 voltage swell
8
L2 voltage swell
9
L3 voltage swell
10 L1
overload
11 L2
overload
12 L3
overload
13 Phase
sequence
error
14
Frequency out of range
15
Q out of range
16 Modbus
communication
error
17 Analogue
output
error
18 Demand
overrun
19
Unexpeted syncron signal
20
Missed syncron signal
Voltage dip:
The voltage value is less than 90% of nominal value.
(Not used the EN50160 standard)
Voltage interrupt:
The voltage value is less than 10% of nominal value.
(Not used the EN50160 standard)
Voltage swell:
The voltage value is more than 110% of nominal value.
110% t. (Not used the EN50160 standard)