PQRM5100 11 Ux Ix xx xx (PS)
52
20200205-V1
6.22. Communication settings
Function
It can be read out through the communication output all of
the measured quantities. The optional communication
option have two operating mode:
•
MODBUS RTU Slave RS485
•
MODBUS ASCII Slave RS485
1. Click on the ”Configuration” tab
2. Inside of ”Configuration” tab click on the “Modul2” tab.
Contents this window depends on device construct.
3. Select the “Protocol” from the “Protocol” pull-down menu.
4. Type-in into the “Modbus Address” field the address of
instrument.
5. Select the “Baud rate” from the “Baud rate” pull-down
menu.
6. Select the “Parity” from the “Parity” pull-down menu.
7. Select the “Stop bit” from the “Stop bit” pull-down menu.
8. Type-in into the “Timeout” field the response timeout of
instrument.
9. Click on the “Save” button.