6.18. Digital output, Demand control function setting
Function
The device calculates the expected average performance
(15 min) from actual power. If this value is greater than the
setting limit, the device set to active state the digital1 output.
If the value is lower than the limit at the next sampling, the
device turn back the digital1 output. If the value is greater
than the setting limit, the device holds the digital1 output to
active state, and the digital2 output sets to active state. At
the next sampling the value of expected average power is
lower the settings limit, the device set the digital2 output to
inactive state.
These outputs states are repeated within a 15 minute
period.
1. Click on the ”Configuration” tab
2. Inside of ”Configuration” tab click on the “Module 1” tab.
3. Select the “Demand 1limit” function on “Function” pull-
down menu.
4. Select the output polarity from the “Polarity” pull-down
menu.
Sequence of operations