7. Select the output function mode from the “Mode” pull-
down menu.
•
Limited mode
The output signal will always remain within the chosen
value (0-20 mA, 4-20 mA)
•
Unlimited mode
The output signal always follows the input signal, between
of range “minimum" and "maximum". The limit of output
signal depends by the analog output circuit (approx. 0-
22mA).
•
Error signal mode
The output signal always follows the input signal, between
of range “minimum" and "maximum". If the value of input
signal falls outside of range “minimum" and "maximum, the
output signal displayed the “Error value”.
8. Type-in into the “Minimum”, into the “Maximum” and into
the “Error signal” field the necessary value of the output
scale.
Pay attention to the value of the " Error value " always fall
for the specified "Minimum" and beyond "Maximum" range,
or can not distinguish between the normal states of the error
state.
9. Click on the “Save” button.