6.9. Current Transformers (CT) ratio settings
Function
The current input of the instrument may connect directly to
the power network (Iin < 5 Aeff [nominal]), or through a
current transformer (Iin > 5 Aeff [nominal]).
When you connect the input directly you should set CT=1.
When you connect the input through a current transformer
you should set the CT ratio of the applied transformer, so
the instrument able to compute with the primary current.
(e.g. 100/5 A/A, CT=20)
[CT Factory default: 1.]
1. Click on the ”Configuration” tab
2. Inside of ”Configuration” tab click on the “Measure
settings” tab.
3. Type the CT ratio value to “I transform” field.
4. Click on the “Save” button.