PQRM5100 11 Ux Ix xx xx (PS)
48
20200205-V1
6.20. Analog output settings
Function
There can be two optional dual independent analog outputs
of the instrument. Any of the measured quantities can be
transmit in a 0 / 4-20 mA current form.
Here you can set all of the parameters of the outputs.
Measured quantities are:
U
12
, U
23
, U
31
, U
L1
, U
L2
, U
L3
, I
L1
, I
L2
, I
L3
,
P
L1
, P
L1
, P
L3
, Q
L1
, Q
L2
, Q
L3
, S
L1
, S
L2
, S
L3
,
PF
L1
, PF
L2
, PF
L3
,
φ
L1
,
φ
L2
,
φ
L3
,
Σ
P,
Σ
Q,
Σ
S,
Σ
PF,
Σφ
, f
1
, f
2
, f
3
;
ρ
12
,
ρ
13
1. Click on the ”Configuration” tab
2. Inside of ”Configuration” tab click on the “Modul2” tab.
Contents this window depends on device construct.
3. Select the desired measured quantity what you are going
to transmit from the “Select” pull-down menu.
4. Type-in into the “Range form” field the lower value of the
output scale.
5. Type-in into the “Range to” field the higher value of the
output scale.
6. Select the output current range (0-20 / 4-20 mA) from the
“Type” pull-down menu.
Sequence of operations
Summary of Contents for PQRM5100 11 U I Series
Page 1: ...PQRM5100 11 Ux Ix xx xx PS Single Phase power transmitter Instruction manual...
Page 76: ...PQRM5100 11 Ux Ix xx xx PS 76 20200205 V1 9 2 Application examples...
Page 77: ...PQRM5100 11 Ux Ix xx xx PS 20200205 V1 77...
Page 78: ...PQRM5100 11 Ux Ix xx xx PS 78 20200205 V1 RS485 bus topology...
Page 79: ...PQRM5100 11 Ux Ix xx xx PS 20200205 V1 79...
Page 80: ......