Detailed description of
the operating mode
(
)
The operating modes define the conditions under which the
limit output should switch ON depending on the value of
the measured and displayed physical signal.
Switched OFF
The output is always switched OFF. [default factory setting]
≥
low limit
It switches ON if the measured value is
≥
low limit.
< low limit
It switches ON if the measured value is < low limit.
Interval between the low and the high limits
It switches ON when (measured value
≥
low limit) AND
(measured value
≤
high limit).
A range outside the low and high limits
It switches ON when (measured value < low limit) OR
(measured value > high limit).
Always switched ON
Independently from the measured value, the output is
always ON.
The essentials about the
hysteresis
To each limit values can be assigned different hysteresis
values.
To
belongs:
,
To
belongs:
.
The essentials about the hysteresis:
It makes it possible that the output should switch off not at
the same numerical value at which it had switched on.
What is the benefit of that? You may avoid the undesired
consequence, when the output switches on and off several
times near the limit values, due to a drift of the input signal,
or due to it’s ripple. This is demonstrated by an example in
the following pictures:
Summary of Contents for DT9000
Page 1: ...DT9000 Intrinsically Safe Process Indicator Operating Instructions...
Page 65: ...DT9000 20171205 V2 65 10 2 Application example...
Page 85: ...DT9000 20171205 V2 85 10 9 ATEX Certification...
Page 86: ...DT9000 86 20171205 V2...
Page 87: ...DT9000 20171205 V2 87...
Page 88: ...DT9000 88 20171205 V2...
Page 89: ...DT9000 20171205 V2 89...
Page 90: ...DT9000 90 20171205 V2...
Page 91: ...DT9000 20171205 V2 91...
Page 92: ...DT9000 92 20171205 V2...
Page 93: ...DT9000 20171205 V2 93...
Page 94: ...DT9000 94 20171205 V2...
Page 95: ...DT9000 20171205 V2 95...
Page 96: ......