7.5. Limit output alarm mode
Function
In alarm mode, the limit output is switching on when the
limit condition exist. But the output stays switched on
(independent from the limit condition) until the
ENTER
button is pressed (alarm acknowledge). (All these
information are described in detail in Chapter
7.4. Setting
up the limit output No. 1.
)
Sequence of operations
1. Enter the menu by the supervisor code.
Chapter
7.1. Typing the code in
describes how you can
type the code in. You see on the display:
.
2. Keep stepping by pressing the
▲
button as long as you
see this menu item:
.
3. Enter the menu item by pressing the
ENTER
button.
4. Keep stepping by pressing the
▲
button as you see this
sub-menu item:
(
A
larm
M
ode).
5. Enter by pressing the
ENTER
button.
6. You see this
on the display. The mnemonic is
blinking.
7. You can switch the alarm mode on by pressing the
▲
button.
•
= the limit output will switch off automatically when
the condition that had caused it to switch on ceases to exist
[default factory setting].
•
= switching the limit output off is possible only by
pressing the ENTER button. It stays switched on, no matter
if the condition that had caused it to switch on ceases to
exist.
Summary of Contents for DT9000
Page 1: ...DT9000 Intrinsically Safe Process Indicator Operating Instructions...
Page 65: ...DT9000 20171205 V2 65 10 2 Application example...
Page 85: ...DT9000 20171205 V2 85 10 9 ATEX Certification...
Page 86: ...DT9000 86 20171205 V2...
Page 87: ...DT9000 20171205 V2 87...
Page 88: ...DT9000 88 20171205 V2...
Page 89: ...DT9000 20171205 V2 89...
Page 90: ...DT9000 90 20171205 V2...
Page 91: ...DT9000 20171205 V2 91...
Page 92: ...DT9000 92 20171205 V2...
Page 93: ...DT9000 20171205 V2 93...
Page 94: ...DT9000 94 20171205 V2...
Page 95: ...DT9000 20171205 V2 95...
Page 96: ......