Example for the practical usage of the limit outputs
There is a 100-litre tank, whose liquid level is indicated by
the instrument DT9000 in 0-100 litres, without decimals.
Task:
The limit output No.1 should control a pump, that switches
ON when the liquid-level goes lower than 70 litres, and
switches OFF when it goes higher than 90 litres.
The limit output No.2 should control a buzzer. The buzzer
should be signalling continuously as long as a manual
acknowledgement takes place, in those cases when the
liquid level goes, at any time, lower than 50 litres, or when
it goes higher than 95 litres.
The settings of the limit outputs are as follows:
operating mode=
(Switches ON, when the
liquid level is lower than the low limit)
Low limit =
Hysteresis of the low limit =
High limit =
(it’s value is indifferent)
Hysteresis of the high limit =
(it’s value is
indifferent)
Alarm mode =
Operating mode=
(Switches ON, when the
liquid level does not fall between the limits.)
Low limit =
Hysteresis of the low limit =
High limit =
Hysteresis of the high limit =
Alarm mode =
Summary of Contents for DT9000
Page 1: ...DT9000 Intrinsically Safe Process Indicator Operating Instructions...
Page 65: ...DT9000 20171205 V2 65 10 2 Application example...
Page 85: ...DT9000 20171205 V2 85 10 9 ATEX Certification...
Page 86: ...DT9000 86 20171205 V2...
Page 87: ...DT9000 20171205 V2 87...
Page 88: ...DT9000 88 20171205 V2...
Page 89: ...DT9000 20171205 V2 89...
Page 90: ...DT9000 90 20171205 V2...
Page 91: ...DT9000 20171205 V2 91...
Page 92: ...DT9000 92 20171205 V2...
Page 93: ...DT9000 20171205 V2 93...
Page 94: ...DT9000 94 20171205 V2...
Page 95: ...DT9000 20171205 V2 95...
Page 96: ......