26-43 Terminal X42/7 Output Bus Control
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the level of terminal X42/7 if controlled by the bus.
26-44 Terminal X42/7 Output Timeout Preset
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the preset level of terminal X42/7.
In case of a bus timeout and a timeout function is selected in par.26-50
, the
output will preset to this level.
26-50 Terminal X42/9 Output
Option:
Function:
Set the function of terminal X42/9.
[0] *
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[113]
Ext. Closed-loop 1
[114]
Ext. Closed-loop 2
[115]
Ext. Closed-loop 3
[139]
Bus ctrl.
[141]
Bus ctrl t.o.
26-51 Terminal X42/9 Min. Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scale the minimum output of the selected analog signal at terminal X42/9, as a percentage of the
maximum signal level, for example if a 0 V is desired at 25% of the maximum output value. Then
program 25%. Scaling values up to 100% can never be higher than the corresponding setting in
par.26-52
See principle graph for par.6-51