26-52 Terminal X42/9 Max. Scale
Range:
Function:
100.00 %* [0.00 - 200.00 %]
Scale the maximum output of the selected analog signal at terminal X42/9. Set the value to the
maximum value of the voltage signal output. Scale the output to give a voltage lower than 10V at
full scale; or 10V at an output below 100% of the maximum signal value. If 10 V is the desired
output current at a value between 0–100% of the full-scale output, program the percentage value
in the parameter, i.e., 50% = 10 V. If a voltage between 0 and 10V is desired at maximum output,
calculate the percentage as follows:
(
10
V
desired
maximum
voltage
)
x
100 %
i.e.
5
V
: 10
V
5
V x
100 % = 200 %
See principle graph for par.6-52
26-53 Terminal X42/9 Output Bus Control
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the level of terminal X42/9 if controlled by bus.
26-54 Terminal X42/9 Output Timeout Preset
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the preset level of terminal X42/9.
In case of a bus timeout and a timeout function is selected in par.26-60
the output will preset to this level.
26-60 Terminal X42/11 Output
Option:
Function:
Set the function of terminal X42/11.
[0] *
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[113]
Ext. Closed-loop 1
[114]
Ext. Closed-loop 2
[115]
Ext. Closed-loop 3
[139]
Bus ctrl.
[141]
Bus ctrl t.o.
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-257
3