Status can be read in the Extended Status Word 2, bit number 24.
24-10 Bypass Function
Option:
Function:
This parameter determines, what circumstances will activate the drive bypass function:
[0] *
Disabled
[1]
Enabled
If in normal operation, the automatic drive bypass function will be activated at following conditions:
At a Trip Lock or a Trip. After the programmed number of reset attempts, programmed in par.
14-20
or if the bypass delay timer (par.24-11
) expires before reset
attempts have been completed
When in fire mode, the bypass function will operate under following conditions:
When experiencing a trip at critical alarms, a coast or if the bypass delay timer expires before reset
attempts have completed when [2] Enabled in fire mode. The bypass function will operate at trip
at critical alarms, coast or if the bypass delay timer expires before reset attempts have been com-
pleted.
[2]
Enabled (Fire Mode Only)
NOTE!
Important! After enabling the drive bypass function, the safe stop function (in versions, where included) no longer complies with
standard EN 954-1, Cat. 3 installations.
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-234