[11]
Analog Input X42/5
[100]
Bus feedback 1
[101]
Bus feedback 2
[102]
Bus feedback 3
NOTE!
If a feedback is not used, its source must be set to
No Function
[0]. par.20-20
determines how the three possible
feedbacks will be used by the PID controller.
20-01 Feedback 1 Conversion
Option:
Function:
This parameter allows a conversion function to be applied to Feedback 1.
[0] *
Linear
Linear
[0] has no effect on the feedback.
[1]
Square root
Square root
[1] is commonly used when a pressure sensor is used to provide flow feedback
(
(
flow
∝
pressure
)
).
[2]
Pressure to temperature
Pressure to temperature
[2] is used in compressor applications to provide temperature feedback
using a pressure sensor. The temperature of the refrigerant is calculated using the following for-
mula:
Temperature
=
A
2
(
ln
(
Pe
+ 1)
−
A
1)
−
A
3
, where A1, A2 and A3 are refrigerant-specific con-
stants. The refrigerant must be selected in par.20-30
allow the values of A1, A2 and A3 to be entered for a refrigerant that is not listed
20-02 Feedback 1 Source Unit
Option:
Function:
This parameter determines the unit that is used for this feedback source, prior to applying the
feedback conversion of par.20-01
. This unit is not used by the PID controller.
[0] *
[1]
%
[5]
PPM
[10]
min
[11]
RPM
[12]
PULSE/s
[20]
liter / sec.
[21]
liter / min
[22]
liter / hr.
[23]
m³ / sec.
[24]
m³/min
[25]
m³ / hr.
[30]
kg / sec.
[31]
kg/min
[32]
kg / hr.
[33]
ton / min
[34]
ton / hr.
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-166
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3