EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%), 0–10 mA
Output signal 0 or 4 mA is needed at Min ref - set par.6-51
to 0%
Output signal 10 mA is needed at Max ref (100% of range) - set par.6-52
to 200%
(20 mA / 10 mA x 100%=200%).
6-53 Terminal 42 Output Bus Control
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the level of Output 42 if controlled by bus.
6-54 Terminal 42 Output Timeout Preset
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the preset level of Output 42.
In case of a bus timeout and a timeout function is selected in par.6-50
, the
output will preset to this level.
3.8.8 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4–20 mA. Common terminal (terminal X30/8) is the same terminal and electrical potential for analog common
connection. Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Option:
Function:
[0] *
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[113]
Ext. Closed-loop 1
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-89