
[1675]
Analog In X30/11
[1676]
Analog In X30/12
[1677]
Analog Out X30/8 [mA]
[1684]
Comm. Option Status
[1685]
FC Port CTW 1
[1690]
Alarm Word
[1691]
Alarm word 2
[1692]
Warning Word
[1693]
Warning word 2
[1694]
Ext. Status Word
[1695]
Ext. Status Word 2
[1696]
Maintenance Word
[1830]
Analog Input X42/1
[1831]
Analog Input X42/3
[1832]
Analog Input X42/5
[1833]
Analog Out X42/7 [V]
[1834]
Analog Out X42/9 [V]
[1835]
Analog Out X42/11 [V]
10-13 Warning Parameter
Range:
Function:
0 N/A*
[0 - 65535 N/A]
View a DeviceNet-specific warning word. One bit is assigned to every warning. Refer to the Devi-
ceNet Instruction Manual (MG.33.DX.YY) for further information.
Bit:
Meaning:
0
Bus not active
1
Explicit connection timeout
2
I/O connection
3
Retry limit reached
4
Actual is not updated
5
CAN bus off
6
I/O send error
7
Initialization error
8
No bus supply
9
Bus off
10
Error passive
11
Error warning
12
Duplicate MAC ID Error
13
RX queue overrun
14
TX queue overrun
15
CAN overrun
10-14 Net Reference
Read only from LCP
Option:
Function:
Select the reference source in instance 21/71 and 20/70.
[0] *
Off
Enables reference via analog/digital inputs.
[1]
On
Enables reference via the serial communication bus.
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-114
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3