NOTE!
The setting in par.14-20
is disregarded in case fire mode is active (see par. 24-0*, Fire Mode).
14-21 Automatic Restart Time
Range:
Function:
10 s*
[0 - 600 s]
Enter the time interval from trip to start of the automatic reset function. This parameter is active
when par.14-20
is set to
Automatic reset
[1] - [13].
14-22 Operation Mode
Option:
Function:
Use this parameter to specify normal operation, to perform tests or to initialize all parameters except
par.15-03
and par.15-05
. This function is active only
when the power is cycled (power off-power on) to the adjustable frequency drive.
[0] *
Normal operation
Select
Normal operation
[0] for normal operation of the adjustable frequency drive with the motor
in the selected application.
[1]
Control card test
Select
Control card test
[1] to test the analog and digital inputs and outputs and the +10 V control
voltage. The test requires a test connector with internal connections.
Use the following procedure for the control card test:
1.
Select
Control card test
[1].
2.
Disconnect the line power supply and wait for the light in the display to go out.
3.
Set switches S201 (A53) and S202 (A54) = ‘ON’ / I.
4.
Insert the test plug (see below).
5.
Connect to the line power supply.
6.
Carry out various tests.
7.
The results are displayed on the LCP and the adjustable frequency drive moves into an
infinite loop.
8.
is automatically set to normal operation. Carry out a power cycle
to start up in normal operation after a control card test.
If the test is OK:
LCP readout: Control Card OK.
Disconnect the line power supply and remove the test plug. The green LED on the control card will
light up.
If the test fails:
LCP readout: Control Card I/O failure.
Replace the adjustable frequency drive or control card. The red LED on the control card is turned
on. To test the plugs, connect/group the following terminals as shown below: (18 - 27 - 32), (19 -
29 - 33) and (42 - 53 - 54).
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-138
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3