[Info]
displays information about a command, parameter, or function in any display window. [Info] provides detailed information when needed.
Exit Info mode by pressing either [Info], [Back], or [Cancel].
Navigation Keys
The four navigation arrows are used to navigate between the different
choices available in
[Quick Menu]
,
[Main Menu]
and
[Alarm Log]
.
Use the keys to move the cursor.
[OK]
is used for choosing a parameter marked by the cursor and for
enabling the change of a parameter.
Operation Keys
for local control are found at the bottom of the control
panel.
130BP046.10
[Hand On]
enables control of the adjustable frequency drive via the GLCP. [Hand On] also starts the motor, and it is now possible to enter the motor speed data by
means of the arrow keys. The key can be selected as
Enable
[1] or
Disable
[0] via par.0-40
The following control signals will still be active when [Hand On] is activated:
•
[Hand On] - [Off] - [Auto on]
•
Reset
•
Coasting stop inverse
•
Reversing
•
Set-up select lsb - Set-up select msb
•
Stop command from serial communication
•
Quick stop
•
DC brake
NOTE!
External stop signals activated by means of control signals or a serial bus will override a “start” command via the LCP.