Operation Keys
Keys for local control are found at the bottom of the control panel.
130BP046.10
Figure 2.5: Operation keys of the numerical CP (NLCP)
[Hand on]
enables control of the adjustable frequency drive via the LCP. [Hand on] also starts the motor and it is now possible to enter the motor speed
data by means of the arrow keys. The key can be selected as
Enable
[1] or
Disable
External stop signals activated by means of control signals or a serial bus will override a 'start' command via the LCP.
The following control signals will still be active when [Hand on] is activated:
•
[Hand on] - [Off] - [Auto on]
•
Reset
•
Coasting stop inverse
•
Reversing
•
Set-up select lsb - Set-up select msb
•
Stop command from serial communication
•
Quick stop
•
DC brake
[Off]
stops the connected motor. The key can be selected as
Enable
[1] or
Disable
If no external stop function is selected and the [Off] key is inactive, the motor can be stopped by disconnecting the line power supply.
[Auto on]
enables the adjustable frequency drive to be controlled via the control terminals and/or serial communication. When a start signal is applied
on the control terminals and/or the bus, the adjustable frequency drive will start. The key can be selected as
Enable
[1] or
Disable
.
NOTE!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control keys [Hand on] [Auto on].
[Reset]
is used for resetting the adjustable frequency drive after an alarm (trip). It can be selected as
Enable
[1] or
Disable
.