3-14 Preset Relative Reference
Range:
Function:
0.00 %*
[-100.00 - 100.00 %]
The actual reference, X, is increased or decreased with the percentage Y, set in par.3-14
. This results in the actual reference Z. Actual reference (X) is the sum of the
inputs selected in par.3-15
, par.3-16
3-15 Reference 1 Source
Option:
Function:
Select the reference input to be used for the first reference signal. par.3-15
define up to three different reference
signals. The sum of these reference signals defines the actual reference.
This parameter cannot be adjusted while the motor is running.
[0]
No function
[1] *
Analog input 53
[2]
Analog input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital pot.meter
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog Input X42/1
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[30]
Ext. Closed-loop 1
[31]
Ext. Closed-loop 2
[32]
Ext. Closed-loop 3
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-35
3