3.8.7 6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog output 1, i.e., Terminal 42. Analog outputs are current outputs: 0/4–20 mA. Common terminal
(terminal 39) is the same terminal and has the same electrical potential for analog common and digital common connection. Resolution on analog output
is 12 bit.
6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as an analog current output. A motor current of 20 mA corre-
sponds to I
max
.
[0] *
No operation
[100]
Output frequency
: 0–100 Hz, (0–20 mA)
[101]
Reference
: Minimum reference - Maximum reference, (0–20 mA)
[102]
Feedback
: -200% to +200% of par.20-14
, (0–20 mA)
[103]
Motor current
: 0 - Inverter Max. Current (par. 16-37), (0–20 mA)
[104]
Torque rel to limit
: 0 - Torque limit (par.4-16
), (0–20 mA)
[105]
Torq relate to rated
: 0 - Motor rated torque, (0–20 mA)
[106]
Power
: 0 - Motor rated power, (0–20 mA)
[107]
Speed
: 0 - Speed High Limit (par.4-13
), (0–20 mA)
[113]
Ext. Closed-loop 1
: 0–100%, (0–20 mA)
[114]
Ext. Closed-loop 2
: 0–100%, (0–20 mA)
[115]
Ext. Closed-loop 3
: 0–100%, (0–20 mA)
[130]
Output freq. 4-20mA
: 0–100 Hz
[131]
Reference 4-20mA
: Minimum Reference - Maximum Reference
[132]
Feedback 4-20mA
: -200% to +200% of par.20-14
[133]
Motor cur. 4-20mA
: 0 - Inverter Max. Current (par.16-37
[134]
Torq.% lim 4-20 mA
: 0 - Torque limit (par.4-16
[135]
Torq.% nom 4-20 mA
: 0 - Motor rated torque
[136]
Power 4-20mA
: 0 - Motor rated power
[137]
Speed 4-20mA
: 0 - Speed High Limit (4-13 and 4-14)
[139]
Bus ctrl.
: 0–100%, (0–20 mA)
[140]
Bus ctrl. 4-20 mA
: 0 - 100%
[141]
Bus ctrl t.o.
: 0–100%, (0–20 mA)
[142]
Bus ctrl 4-20mA t.o.
: 0 - 100%
[143]
Ext. Closed-loop 1 4-20 mA
: 0 - 100%
[144]
Ext. Closed-loop 2 4-20 mA
: 0 - 100%
[145]
Ext. Closed-loop 3 4-20 mA
: 0 - 100%
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-86
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3