Ordering type codemodel number frame size F
Description
Pos
Possible choice
Product group
1-3
FC 302
Drive series
4-6
FC 302
Power rating
8-10
450 - 1200 kW
Phases
11
Three phases (T)
Mains voltage
11-
12
T 5: 380-500V AC
T 7: 525-690V AC
Enclosure
13-
15
C21: IP21/NEMA Type 1 with stainless steel
back channel
C54: IP54/Type 12 Stainless steel back
channel
E21: IP 21/ NEMA Type 1
E54: IP 54/ NEMA Type 12
L2X: IP21/NEMA 1 with cabinet light & IEC
230V power outlet
L5X: IP54/NEMA 12 with cabinet light & IEC
230V power outlet
L2A: IP21/NEMA 1 with cabinet light & NAM
115V power outlet
L5A: IP54/NEMA 12 with cabinet light & NAM
115V power outlet
H21: IP21 with space heater and thermostat
H54: IP54 with space heater and thermostat
R2X: IP21/NEMA1 with space heater,
thermostat, light & IEC 230V outlet
R5X: IP54/NEMA12 with space heater,
thermostat, light & IEC 230V outlet
R2A: IP21/NEMA1 with space heater,
thermostat, light, & NAM 115V outlet
R5A: IP54/NEMA12 with space heater,
thermostat, light, & NAM 115V outlet
RFI filter
16-
17
H2: RFI filter, class A2 (standard)
H4: RFI filter, class A1
2, 3)
HE: RCD with Class A2 RFI filter
2)
HF: RCD with class A1 RFI filter
2, 3)
HG: IRM with Class A2 RFI filter
2)
HH: IRM with class A1 RFI filter
2, 3)
HJ: NAMUR terminals and class A2 RFI filter
1)
HK: NAMUR terminals with class A1 RFI filter
1,
2, 3)
HL: RCD with NAMUR terminals and class A2
RFI filter
1, 2)
HM: RCD with NAMUR terminals and class A1
RFI filter
1, 2, 3)
HN: IRM with NAMUR terminals and class A2
RFI filter
1, 2)
HP: IRM with NAMUR terminals and class A1
RFI filter
1, 2, 3)
N2: Low Harmonic Drive with RFI filter, class
A2
N4: Low Harmonic Drive with RFI filter, class
A1
B2: 12-pulse drive with RFI filter, class A2
B4: 12-pulse drive with RFI filter, class A1
BE: 12-pulse + RCD for TN/TT Mains + Class
A2 RFI
BF: 12-pulse + RCD for TN/TT Mains + Class
A1 RFI
BG: 12-pulse + IRM for IT Mains + Class A2
RFI
BH: 12-pulse + IRM for IT Mains + Class A1
RFI
BM: 12-pulse + RCD for TN/TT Mains +
NAMUR Ter Class A1 RFI*
Brake
18
B: Brake IGBT mounted
X: No brake IGBT
C: Safe Stop with Pilz Relay
D : Safe Stop with Pilz Safety Relay & Brake
IGBT
R: Regeneration terminals
M: IEC Emergency stop pushbutton (with Pilz
safety relay)
4)
N: IEC Emergency stop pushbutton with
brake IGBT and brake terminals
4)
P: IEC Emergency stop pushbutton with
regeneration terminals
4)
Display
19
G: Graphical Local Control Panel LCP
Coating PCB
20
C: Coated PCB
Mains option
21
X: No mains option
3
2)
: Mains disconnect and Fuse
5
2)
: Mains disconnect, Fuse and Load sharing
7: Fuse
A: Fuse and Load sharing
D: Load sharing
E: Mains disconnect, contactor & fuses
2)
F: Mains circuit breaker, contactor & fuses
2)
G: Mains disconnect, contactor, loadsharing
terminals & fuses
2)
H: Mains circuit breaker, contactor,
loadsharing terminals & fuses
2)
J: Mains circuit breaker & fuses
2)
K: Mains circuit breaker, loadsharing terminals
& fuses
2)
* Requires MCB 112 ans MCB 113
Description
Pos
Possible choice
Power Terminals
& Motor Starters
22
X: No option
E 30 A, fuse-protected power terminals
F: 30A, fuse-protected power terminals &
2.5-4 A manual motor starter
G: 30A, fuse-protected power terminals &
4-6.3 A manual motor starter
H: 30A, fuse-protected power terminals &
6.3-10 A manual motor starter
J: 30A, fuse-protected power terminals &
10-16 A manual motor starter
K: Two 2.5-4 A manual motor starters
L: Two 4-6.3 A manual motor starters
M: Two 6.3-10 A manual motor starters
N: Two 10-16 A manual motor starters
Auxiliary 24V
Supply &
External
Temperature
Monitoring
23
X: No option
H: 5A, 24V power supply (customer use)
J: External temperature monitoring
G: 5A, 24V power supply (customer use) &
external temperature monitoring
Software release 24-
27
Actual software
24-
28
S023 : 316 Stainless Steel Backchannel - high
power drives only
Software
language
28
1) MCB 113 Extended Relay Card and MCB 112 PTC Thermistor Card
required for NAMUR terminals
2) F3 and F4 frames only
3) 380-480/500V only
4) Requires contactor
How to Order
FC 300 Design Guide
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
97
5
5