Mains Supply 3 x 525- 690V AC
FC 302
P37K
P45K
P55K
P75K
P90K
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output at
550V [kW]
30
37
37
45
45
55
55
75
75
90
Typical Shaft output at
575V [HP]
40
50
50
60
60
75
75
100
100
125
Typical Shaft output at
690V [kW]
37
45
45
55
55
75
75
90
90
110
Enclosure IP21
D1
D1
D1
D1
D1
Enclosure IP54
D1
D1
D1
D1
D1
Enclosure IP00
D3
D3
D3
D3
D3
Output current
Continuous
(at 550V) [A]
48
56
56
76
76
90
90
113
113
137
Intermittent (60 sec
overload)
(at 550V) [A]
77
62
90
84
122
99
135
124
170
151
Continuous
(at 575/690V) [A]
46
54
54
73
73
86
86
108
108
131
Intermittent (60 sec
overload)
(at 575/690V) [A]
74
59
86
80
117
95
129
119
162
144
Continuous KVA
(at 550V) [KVA]
46
53
53
72
72
86
86
108
108
131
Continuous KVA
(at 575V) [KVA]
46
54
54
73
73
86
86
108
108
130
Continuous KVA
(at 690V) [KVA]
55
65
65
87
87
103
103
129
129
157
Max. input current
Continuous
(at 550V ) [A]
53
60
60
77
77
89
89
110
110
130
Continuous
(at 575V ) [A]
51
58
58
74
74
85
85
106
106
124
Continuous
(at 690V) [A]
50
58
58
77
77
87
87
109
109
128
Max. cable size, mains,
motor, load share and
brake [mm
2
(AWG)]
2x70 (2x2/0)
Max. external mains
fuses [A]
1
125
160
200
200
250
Estimated power loss
at 600V [W]
4)
1299
1398
1459
1645
1643
1827
1350
1599
1597
1891
Estimated power loss
at 690V [W]
4)
1002
1071
1071
1251
1251
1392
1392
1648
1650
1951
Weight,
enclosure IP21, IP54 [kg]
96
Weight,
enclosure IP00 [kg]
82
Efficiency
4)
0.97
0.97
0.98
0.98
0.98
Output frequency
0 - 600Hz
Heatsink overtemp. trip
90
°
C
Power card ambient trip
75
°
C
* High overload = 160% torque during 60 sec., Normal overload = 110% torque during 60 sec.
FC 300 Selection
FC 300 Design Guide
76
MG.33.BD.02 - VLT
®