8.6.7 Electrical Installation, Control Cables
3 Phase
power
input
DC bus
Switch Mode
Power Supply
Motor
Analog Output
Interface
relay1
* relay2
ON=Terminated
OFF=Open
Brake
resistor
130BA025.20
91 (L1)
92 (L2)
93 (L3)
PE
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24V OUT)
13 (+24V OUT)
37 (D IN)
18 (D IN)
20 (COM D IN)
10Vdc
15mA 130/200mA
+
-
+
-
(U) 96
(V) 97
(W) 98
(PE) 99
(COM A OUT) 39
(A OUT) 42
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0V
5V
S801
0/4-20 mA
RS-485
RS-485
03
+10Vdc
0/-10Vdc -
+10Vdc
+10Vdc
0/4-20 mA
0/-10Vdc -
240Vac, 2A
24Vdc
02
01
05
04
06
240Vac, 2A
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
19 (D IN)
24V (NPN)
0V (PNP)
27
24V
0V
(D IN/OUT)
0V (PNP)
24V (NPN)
(D IN/OUT)
0V
24V
29
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
33 (D IN)
32 (D IN)
1
2
ON
S201
ON
2
1S202
ON=0/4-20mA
OFF=0/-10Vdc -
+10Vdc
95
400Vac, 2A
P 5-00
2
1
ON
S801
(R+) 82
(R-) 81
*
*
Illustration 8.60 Diagram showing all electrical terminals without options.
A = analog, D = digital
Terminal 37 is used for Safe Stop. For instructions on Safe Stop installation please refer to the section
Safe Stop Installation
of the Design
Guide.
* Terminal 37 is not included in FC 301 (Except FC 301 A1, which includes Safe Stop).
Relay 2 and Terminal 29, have no function in FC 301.
Very long control cables and analogue signals may in rare cases and depending on installation result in 50/60 Hz earth
loops due to noise from mains supply cables. If this occurs, it may be necessary to break the screen or insert a 100 nF
capacitor between screen and chassis. The digital and analogue inputs and outputs must be connected separately to the
common inputs (terminal 20, 55, 39) of the frequency converter to avoid ground currents from both groups to affect other
groups. For example, switching on the digital input may disturb the analog input signal.