FC 300, P1K5T4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
5
480
0.640
0.690
0.862
50
480
0.470
0.985
0.985
150
480
0.760
1.045
0.947
FC 300, P4K0T4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
5
480
0.172
0.890
4.156
50
480
0.310
2.564
150
480
0.370
1.190
1.770
FC 300, P7K5T4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
5
480
0.04755
0.739
8.035
50
480
0.207
4.548
150
480
0.6742
1.030
2.828
FC 300, P11KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
36
480
0.396
1.210
2.444
100
480
0.844
1.230
1.165
150
480
0.696
1.160
1.333
FC 300, P15KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
36
480
0.396
1.210
2.444
100
480
0.844
1.230
1.165
150
480
0.696
1.160
1.333
FC 300, P18KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
36
480
0.312
2.846
100
480
0.556
1.250
1.798
150
480
0.608
1.230
1.618
FC 300, P22KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
15
480
0.288
3.083
100
480
0.492
1.230
2.000
150
480
0.468
1.190
2.034
FC 300, P30KT4
Cable
length [m]
Mains
voltage
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
5
480
0.368
1.270
2.853
50
480
0.536
1.260
1.978
100
480
0.680
1.240
1.426
150
480
0.712
1.200
1.334
FC 300, P37KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
5
480
0.368
1.270
2.853
50
480
0.536
1.260
1.978
100
480
0.680
1.240
1.426
150
480
0.712
1.200
1.334
FC 300, P45KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
15
480
0.256
1.230
3.847
50
480
0.328
1.200
2.957
100
480
0.456
1.200
2.127
150
480
0.960
1.150
1.052
FC 300, P55KT5
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
5
480
0.371
1.170
2.523
FC 300, P75KT5
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
5
480
0.371
1.170
2.523
FC 300 Selection
FC 300 Design Guide
92
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
4
4