4 FC 300 Selection
4.1 Electrical Data - 200-240V
Mains Supply 3 x 200 - 240V AC
FC 301/FC 302
PK25
PK37
PK55
PK75
P1K1
P1K5
P2K2
P3K0
P3K7
Typical Shaft Output [kW]
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
3.7
Enclosure IP20/IP21
A2
A2
A2
A2
A2
A2
A2
A3
A3
EnclosureIP 20 (FC 301 only)
A1
A1
A1
A1
A1
A1
-
-
-
Enclosure IP55, 66
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output current
Continuous
(3 x 200-240V ) [A]
1.8
2.4
3.5
4.6
6.6
7.5
10.6
12.5
16.7
Intermittent
(3 x 200-240V ) [A]
2.9
3.8
5.6
7.4
10.6
12.0
17.0
20.0
26.7
Continuous
kVA (208V AC) [kVA]
0.65
0.86
1.26
1.66
2.38
2.70
3.82
4.50
6.00
Max. input current
Continuous
(3 x 200-240V ) [A]
1.6
2.2
3.2
4.1
5.9
6.8
9.5
11.3
15.0
Intermittent
(3 x 200-240V ) [A]
2.6
3.5
5.1
6.6
9.4
10.9
15.2
18.1
24.0
Additional specifications
IP20, 21 max. cable cross section
5)
(mains, motor, brake and load
sharing) [mm
2
(AWG )]
2)
4,4,4 (12,12,12)
(min. 0.2(24))
IP55, 66 max. cable cross section
5)
(mains, motor, brake and load
sharing) [mm
2
(AWG)]
4,4,4 (12,12,12)
Max. cable cross section
5)
with
disconnect
6,4,4 (10,12,12)
Estimated power loss
at rated max. load [W]
4)
21
29
42
54
63
82
116
155
185
Weight, enclosure IP20 [kg]
4.7
4.7
4.8
4.8
4.9
4.9
4.9
6.6
6.6
A1 (IP20)
2.7
2.7
2.7
2.7
2.7
2.7
-
-
-
A5 (IP55, 66)
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
Efficiency
4)
0.94
0.94
0.95
0.95
0.96
0.96
0.96
0.96
0.96
0.25 - 3.7kW only available as 160% high overload.
FC 300 Selection
FC 300 Design Guide
60
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
4
4