10.1.3 Mounting of Options in Slot C
The power to the frequency converter must be discon-
nected.
It is strongly recommended to make sure the parameter
data is saved (i.e. by MCT 10 software ) before option
modules are inserted/removed from the drive.
When installing a C option, a mounting kit is required.
Please refer to the
How to Order
section for a list of
ordering numbers. The installation is illustrated using MCB
112 as an example. For more information on installation of
MCO 305, see separate operating instructions.
130BA946.10
Remo
veJumper t
o ac
tivate S
afe St
op
12 13 18 19 27 29 32 33 20
Illustration 10.3 Frame sizes A2, A3 and B3
DC
DC
130BA945.10
Illustration 10.4 Frame sizes A5, B1, B2, B4, C1, C2, C3 and C4
If both C0 and C1 options are to be installed, the instal-
lation is carried out as shown below. Note that this is only
possible for frame sizes A2, A3 and B3.
Remo
veJumpe
r to ac
tivate S
afe Stop
12 13 18 19 27 29 32 33 20
130BA947.10
Illustration 10.5 Frame sizes A2, A3 and B3
10.2 General Purpose Input Output Module
MCB 101
MCB 101 is used for extension of digital and analog inputs
and outputs of FC 301 and FC 302.
Contents: MCB 101 must be fitted into slot B in the VLT
AutomationDrive.
•
MCB 101 option module
•
Extended fixture for LCP
•
Terminal cover
General Purpose I/O
SW. ver. XX.XX
MCB 101
FC Series
Code No. 130BXXXX
B slot
X30/
AIN4
7
8
6
5
4
3
2
1
9
10
11
12
AIN3
GND(2)
24V
AOUT2
DOUT4
DOUT3
GND(1)
DIN7
CO
M
DIN
DIN8
DIN9
130BA208.10
10.2.1 Galvanic Isolation in the MCB 101
Digital/analog inputs are galvanically isolated from other
inputs/outputs on the MCB 101 and in the control card of
the frequency converter. Digital/analog outputs in the MCB
101 are galvanically isolated from other inputs/outputs on
the MCB 101, but not from these on the control card of
the drive.
If the digital inputs 7, 8 or 9 are to be switched by use of
the internal 24V power supply (terminal 9) the connection
Options and Accessories
FC 300 Design Guide
236
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
10
10