8 Electrical Installation
8.1 Connections- Frame Sizes A, B and C
NOTE
Cables General
All cabling must comply with national and local
regulations on cable cross-sections and ambient
temperature. Copper (75
°
C) conductors are recommended.
Aluminium Conductors
Terminals can accept aluminium conductors but the
conductor surface has to be clean and the oxidation must
be removed and sealed by neutral acid-free Vaseline
grease before the conductor is connected.
Furthermore the terminal screw must be retightened after
two days due to softness of the aluminium. It is crucial to
keep the connection a gas tight joint, otherwise the
aluminium surface will oxidize again.
Tightening-up Torque
Frame size
200 - 240 V
380 - 500 V
525 - 690 V
Cable for:
Tightening up torque
A1
0.25-1.5 kW
0.37-1.5 kW
-
Mains, Brake resistor, load sharing, Motor cables
0.5-0.6 Nm
A2
0.25-2.2 kW
0.37-4 kW
-
A3
3-3.7 kW
5.5-7.5 kW
-
A4
0.25-2-2 kW
0.37-4 kW
A5
3-3.7 kW
5.5-7.5 kW
-
B1
5.5-7.5 kW
11-15 kW
-
Mains, Brake resistor, load sharing, Motor cables
1.8 Nm
Relay
0.5-0.6 Nm
Earth
2-3 Nm
B2
11 kW
18.5-22 kW
11-22 kW
Mains, Brake resistor, load sharing cables
4.5 Nm
Motor cables
4.5 Nm
Relay
0.5-0.6 Nm
Earth
2-3 Nm
B3
5.5-7.5 kW
11-15 kW
-
Mains, Brake resistor, load sharing, Motor cables
1.8 Nm
Relay
0.5-0.6 Nm
Earth
2-3 Nm
B4
11-15 kW
18.5-30 kW
-
Mains, Brake resistor, load sharing, Motor cables
4.5 Nm
Relay
0.5-0.6 Nm
Earth
2-3 Nm
C1
15-22 kW
30-45 kW
-
Mains, Brake resistor, load sharing cables
10 Nm
Motor cables
10 Nm
Relay
0.5-0.6 Nm
Earth
2-3 Nm
C2
30-37 kW
55-75 kW
30-75 kW
Mains, motor cables
14 Nm (up to 95 mm
2
)
24 Nm (over 95 mm
2
)
Load Sharing, brake cables
14 Nm
Relay
0.5-0.6 Nm
Earth
2-3 Nm
C3
18.5-22 kW
30-37 kW
-
Mains, Brake resistor, load sharing, Motor cables
10 Nm
Relay
0.5-0.6 Nm
Earth
2-3 Nm
C4
37-45 kW
55-75 kW
-
Mains, motor cables
14 Nm (up to 95 mm
2
)
24 Nm (over 95 mm
2
)
Load Sharing, brake cables
14 Nm
Relay
0.5-0.6 Nm
Earth
2-3 Nm
Electrical Installation
FC 300 Design Guide
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
157
8