Mains Supply 3 x 380 - 500V AC (FC 302), 3 x 380 - 480V AC (FC 301)
FC 301/FC 302
P30K
P37K
P45K
P55K
P75K
High/ Normal Load
1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output [kW]
30
37
37
45
45
55
55
75
75
90
Enclosure IP20
B4
C3
C3
C4
C4
Enclosure IP21
C1
C1
C1
C2
C2
Enclosure IP55, 66
C1
C1
C1
C2
C2
Output current
Continuous
(3 x 380-440V) [A]
61
73
73
90
90
106
106
147
147
177
Intermittent (60 sec.
overload)
(3 x 380-440V) [A]
91.5
80.3
110
99
135
117
159
162
221
195
Continuous
(3 x 441-500V) [A]
52
65
65
80
80
105
105
130
130
160
Intermittent (60 sec
overload)
(3 x 441-500V) [A]
78
71.5
97.5
88
120
116
158
143
195
176
Continuous kVA
(400V AC) [kVA]
42.3
50.6
50.6
62.4
62.4
73.4
73.4
102
102
123
Continuous kVA
(460V AC) [kVA]
51.8
63.7
83.7
104
128
Max. input current
Continuous
(3 x 380-440V) [A]
55
66
66
82
82
96
96
133
133
161
Intermittent (60 sec
overload)
(3 x 380-440V) [A]
82.5
72.6
99
90.2
123
106
144
146
200
177
Continuous
(3 x 441-500V) [A]
47
59
59
73
73
95
95
118
118
145
Intermittent (60 sec
overload)
(3 x 441-500V) [A]
70.5
64.9
88.5
80.3
110
105
143
130
177
160
Additional specifications
IP20 max. cable cross-
section
5)
(mains and
motor)
35 (2)
50 (1)
50 (1)
150 (300mcm)
150 (300mcm)
IP20 max. cable cross-
section
5)
(brake and load
sharing)
35 (2)
50 (1)
50 (1)
95 (4/0)
95 (4/0)
IP21, 55, 66 max. cable
cross-section
5)
(mains,
motor) [mm
2
(AWG)]
2)
50 (1)
50 (1)
50 (1)
150 (300MCM)
150 (300MCM)
IP21, 55, 66 max. cable
cross-section
5)
(brake, load
sharing) [mm
2
(AWG)]
2)
50 (1)
50 (1)
50 (1)
95 (3/0)
95 (3/0)
Max cable size with mains
disconnect [mm
2
(AWG)]
2)
50, 35, 35
(1, 2, 2)
95, 70, 70
(3/0, 2/0, 2/0)
185, 150, 120
(350MCM, 300MCM,
4/0)
Estimated power loss
at rated max. load [W]
4)
570
698
697
843
891
1083
1022
1384
1232
1474
Weight,
enclosure IP21, IP55, 66
[kg]
45
45
45
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
0.99
For fuse ratings, see 8.3.1 Fuses
1) High overload = 160% torque during 60 sec., Normal overload = 110% torque during 60 sec.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerence relates to variety in voltage and
cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the
frequency converter and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses.
(Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
5) The three values for the max. cable cross section are for single core, flexible wire and flexible wire with sleeve, respectively.
FC 300 Selection
FC 300 Design Guide
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
65