Bit 12, Drive OK/Stopped, autostart
When bit 12 = "0", there is no temporary overloading of
the inverter.
When bit 12 = "1", the inverter has stopped due to
overloading. However, the frequency converter has not
switched off (trip) and will start again after the overloading
has ended.
Bit 13, Voltage OK/Voltage exceeded
When bit 13 = "0", the voltage limits of the frequency
converter are not exceeded.
When bit 13 = "1", the direct voltage in the intermediate
circuit of the frequency converter is too low or too high.
Bit 14, Torque OK/Torque exceeded
When bit 14 = "0", the motor torque is below the limit
selected in
4-16 Torque Limit Motor Mode
and
4-17 Torque
Limit Generator Mode
. When bit 14 = "1", the limit selected
in
4-16 Torque Limit Motor Mode
or
4-17 Torque Limit
Generator Mode
is exceeded.
Bit 15, Timer OK/Timer exceeded
When bit 15 = "0", the timers for the thermal motor
protection and thermal frequency converter protection
have not exceeded 100%.
When bit 15 = "1", one of the timers has exceeded 100%.