4.2 Electrical Data - 380-500V
Mains Supply 3 x 380 - 500V AC (FC 302), 3 x 380 - 480V AC (FC 301)
PK 37
PK 55
PK75
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
FC 301/FC 302
Typical Shaft Output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Enclosure IP20/IP21
A2
A2
A2
A2
A2
A2
A2
A2
A3
A3
Enclosure IP20 (FC 301 only)
A1
A1
A1
A1
A1
Enclosure IP55, 66
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output current
High overload 160% for 1 min.
Shaft output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Continuous
(3 x 380-440V) [A]
1.3
1.8
2.4
3
4.1
5.6
7.2
10
13
16
Intermittent
(3 x 380-440V) [A]
2.1
2.9
3.8
4.8
6.6
9.0
11.5
16
20.8
25.6
Continuous
(3 x 441-500V) [A]
1.2
1.6
2.1
2.7
3.4
4.8
6.3
8.2
11
14.5
Intermittent
(3 x 441-500V) [A]
1.9
2.6
3.4
4.3
5.4
7.7
10.1
13.1
17.6
23.2
Continuous kVA
(400V AC) [kVA]
0.9
1.3
1.7
2.1
2.8
3.9
5.0
6.9
9.0
11.0
Continuous kVA
(460V AC) [kVA]
0.9
1.3
1.7
2.4
2.7
3.8
5.0
6.5
8.8
11.6
Max. input current
Continuous
(3 x 380-440V) [A]
1.2
1.6
2.2
2.7
3.7
5.0
6.5
9.0
11.7
14.4
Intermittent
(3 x 380-440V) [A]
1.9
2.6
3.5
4.3
5.9
8.0
10.4
14.4
18.7
23.0
Continuous
(3 x 441-500V) [A]
1.0
1.4
1.9
2.7
3.1
4.3
5.7
7.4
9.9
13.0
Intermittent
(3 x 441-500V) [A]
1.6
2.2
3.0
4.3
5.0
6.9
9.1
11.8
15.8
20.8
Additional specifications
IP20, 21 max. cable cross
section
5)
(mains, motor, brake
and load sharing) [mm
2
(AWG )]
2)
4,4,4 (12,12,12)
(min. 0.2(24))
IP55, 66 max. cable cross
section
5)
(mains, motor, brake
and load sharing) [mm
2
(AWG)]
4,4,4 (12,12,12)
Max. cable cross section
5)
with
disconnect
6,4,4 (10,12,12)
Estimated power loss
at rated max. load [W]
4)
35
42
46
58
62
88
116
124
187
255
Weight,
enclosure IP20
4.7
4.7
4.8
4.8
4.9
4.9
4.9
4.9
6.6
6.6
Enclosure IP55, 66
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
14.2
14.2
Efficiency
4)
0.93
0.95
0.96
0.96
0.97
0.97
0.97
0.97
0.97
0.97
0.37 - 7.5 kW only available as 160% high overload.
FC 300 Selection
FC 300 Design Guide
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
63
4
4