6-60 Terminal X30/8 Output
Option:
Function:
[0] *
No operation
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Fe-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[113]
Ext. Closed Loop 1
: 0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2
: 0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3
: 0 - 100%, (0-20 mA)
[130]
Out frq 0-100 4-20mA
[131]
Reference 4-20mA
: Minimum Reference - Maximum Reference
[132]
Feedback 4-20mA
: -200% to +200% of par. 20-14
Maximum Reference/Feedb.
[133]
Motor cur. 4-20mA
: 0 - Inverter Max. Current (par.16-37
[134]
Torq.0-lim 4-20 mA
[135]
Torq.0-nom 4-20mA
[136]
Power 4-20mA
: 0 - Motor rated power
[137]
Speed 4-20mA
: 0 - Speed High Limit (4-13 and 4-14)
[139]
Bus ctrl.
: 0 - 100%, (0-20 mA)
[140]
Bus ctrl. 4-20 mA
: 0 - 100%
[141]
Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
[142]
Bus ctrl t.o. 4-20mA
: 0 - 100%
[143]
Ext. CL 1 4-20mA
: 0 - 100%
[144]
Ext. CL 2 4-20mA
: 0 - 100%
[145]
Ext. CL 3 4-20mA
: 0 - 100%
6-61 Terminal X30/8 Min. Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scales the minimum output of the selected analog signal on terminal X30/8. Scale the minimum
value as a percentage of the maximum signal value, i.e. 0 mA (or 0 Hz) is desired at 25% of the
maximum output value and 25% is programmed. The value can never be higher than the corre-
sponding setting in par.6-62
This parameter is active when option module MCB 101 is mounted in the frequency converter.
2 Parameter Description
VLT
®
AQUA Drive Programming Guide
94