9-27 Parameter Edit
Option:
Function:
Parameters can be edited via Profibus, the standard RS485 interface, or the LCP.
[0]
Disabled
Disables editing via Profibus.
[1] *
Enabled
Enables editing via Profibus.
9-28 Process Control
Option:
Function:
Process control (setting of Control Word, speed reference, and process data) is possible via either
Profibus or standard fieldbus but not both simultaneously. Local control is always possible via the
LCP. Control via process control is possible via either terminals or fieldbus depending on the settings
in par.8-50
[0]
Disable
Disables process control via Profibus, and enables process control via standard fieldbus or Profibus
Master class 2.
[1] *
Enable cyclic master
Enables process control via Profibus Master Class 1, and disables process control via standard field-
bus or Profibus Master class 2.
9-53 Profibus Warning Word
Range:
Function:
0 N/A*
[0 - 65535 N/A]
This parameter displays Profibus communication warnings. Please refer to the
Profibus Operating
Instructions
for further information.
Read only
Bit:
Meaning:
0
Connection with DP-master is not ok
1
Not used
2
FDLNDL (Fieldbus Data link Layer) is not ok
3
Clear data command received
4
Actual value is not updated
5
Baudrate search
6
PROFIBUS ASIC is not transmitting
7
Initializing of PROFIBUS is not ok
8
Frequency converter is tripped
9
Internal CAN error
10
Wrong configuration data from PLC
11
Wrong ID sent by PLC
12
Internal error occured
13
Not configured
14
Timeout active
15
Warning 34 active
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
109