NB!
Sleep Mode will not be active when Local Reference is active (set speed manually by means of arrow buttons on the Local Control
Panel). See Par. 3-13,
Reference Site
.
Does not work in Hand-mode. Auto set-up in open loop must be carried out before setting input/output in closed loop.
22-40 Minimum Run Time
Range:
Function:
10 s*
[0 - 600 s]
Set the desired minimum running time for the motor after a start command (digital input or Bus)
before entering Sleep Mode.
22-41 Minimum Sleep Time
Range:
Function:
10 s*
[0 - 600 s]
Set the desired Minimum Time for staying in Sleep Mode. This will override any wake up conditions.
22-42 Wake-up Speed [RPM]
Range:
Function:
0 RPM*
[par. 4-11 - par. 4-13 RPM]
To be used if par.0-02
has been set for RPM (parameter not visible if Hz selected).
Only to be used if par.1-00
is set for Open Loop and speed reference is applied
by an external controller.
Set the reference speed at which the Sleep Mode should be cancelled.
22-43 Wake-up Speed [Hz]
Range:
Function:
0 Hz*
[par. 4-12 - par. 4-14 Hz]
To be used if par.0-02
, has been set for Hz (parameter not visible if RPM selected).
Only to be used if par.1-00
, is set for Open Loop and speed reference is applied
by an external controller controlling the pressure.
Set the reference speed at which the Sleep Mode should be cancelled.
22-44 Wake-up Ref./FB Difference
Range:
Function:
10%*
[0-100%]
Only to be used if par. 1-00,
Configuration Mode
, is set for Closed Loop and the integrated PI
controller is used for controlling the pressure.
Set the pressure drop allowed in percentage of set point for the pressure (Pset) before cancelling
the Sleep Mode.
NB!
If used in application where the integrated PI controller is set for inverse control
in par. 20-71,
PID, Normal/Inverse Control
, the value set in par. 22-44 will au-
tomatically be added.
22-45 Setpoint Boost
Range:
Function:
0 %*
[-100 - 100 %]
Only to be used if par.1-00
, is set for Closed Loop and the integrated PI con-
troller is used. In systems with e.g. constant pressure control, it is advantageous to increase the
system pressure before the motor is stopped. This will extend the time in which the motor is stopped
and help to avoid frequent start/stop.
Set the desired over pressure/temperature in percentage of set point for the pressure (Pset)/tem-
perature before entering the Sleep Mode.
If setting for 5%, the boost pressure will be Pset*1.05. The negative values can be used for e.g.
cooling tower control where a negative change is needed.