Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/2
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/4
Bit 10-63
Reserved for future terminals
16-61 Terminal 53 Switch Setting
Option:
Function:
View the setting of input terminal 53. Current = 0; Voltage = 1.
[0] *
Current
[1]
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
16-62 Analog Input 53
Range:
Function:
0.000 N/A* [-20.000 - 20.000 N/A]
View the actual value at input 53.
16-63 Terminal 54 Switch Setting
Option:
Function:
View the setting of input terminal 54. Current = 0; Voltage = 1.
[0] *
Current
[1]
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
16-64 Analog Input 54
Range:
Function:
0.000 N/A* [-20.000 - 20.000 N/A]
View the actual value at input 54.
16-65 Analog Output 42 [mA]
Range:
Function:
0.000 N/A* [0.000 - 30.000 N/A]
View the actual value at output 42 in mA. The value shown reflects the selection in par.6-50
.
16-66 Digital Output [bin]
Range:
Function:
0 N/A*
[0 - 15 N/A]
View the binary value of all digital outputs.
2 Parameter Description
VLT
®
AQUA Drive Programming Guide
154
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
2