2.21 Main Menu - Cascade Controller - Group 25
2.21.1 25-** Cascade Controller
Parameters for configuring the Basic Cascade Controller for sequence control of multiple pumps. For a more application oriented description and wiring
examples, see section
Application Examples, Basic Cascade Controller
.
To configure the Cascade Controller to the actual system and the desired control strategy, it is recommended to follow the below sequence, starting with
par. 25-0*
System Settings
and next par. 25-5*
Alternation Settings
. These parameter can normally be set in advance.
Parameters in 25-2*
Bandwidth Settings
and 25-4*
Staging settings
, will often be dependent on the dynamic of the system and final adjustment to be
done at the commissioning of the plant.
NB!
The Cascade Controller is supposed to operate in closed loop controlled by the built-in PI controller (Closed Loop selected in
Configu-
ration Mode
Open Loop
is selected in par.1-00
, all fixed speed pumps will be
destaged, but the variable speed pump will still be controlled by the frequency converter, now as an open loop configuration:
2 Parameter Description
VLT
®
AQUA Drive Programming Guide
212
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
2