NB!
Resets parameters selected in Personal Menu with default factory setting.
initialises all except:
par. 14-50
RFI Filter
par. 8-30
Protocol
to par.15-22
to par.15-32
Manual initialisation
1.
Disconnect from mains and wait until the display turns off.
2a.
Press [Status] - [Main Menu] - [OK] at the same time while power up for LCP 102, Graphical Display
2b.
Press [Menu] while power up for LCP 101, Numerical Display
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed according to default settings.
This procedure initializes all except: par.15-00
NB!
When you carry out manual initialisation, you also reset serial communication, par. 14-50
RFI Filter
and fault log settings.
Removes parameters selected in par.25-00
NB!
After initialization and power cycling, the display will not show any information until after a couple of minutes.