2.11 Main Menu - CAN Fieldbus - Group 10
2.11.1 10-** DeviceNet and CAN Fieldbus
Parameter group for DeviceNet CAN fieldbus parameters.
2.11.2 10-0* Common Settings
Parameter group for configuring common settings for CAN fieldbus options.
10-00 CAN Protocol
Option:
Function:
[1] *
DeviceNet
View the active CAN protocol.
NB!
The options depend on installed option
10-01 Baud Rate Select
Option:
Function:
Select the fieldbus transmission speed. The selection must correspond to the transmission speed of
the master and the other fieldbus nodes.
[16]
10 Kbps
[17]
20 Kbps
[18]
50 Kbps
[19]
100 Kbps
[20] *
125 Kbps
[21]
250 Kbps
[22]
500 Kbps
[23]
800 Kbps
[24]
1000 Kbps
10-02 MAC ID
Range:
Function:
63. N/A*
[0 - 63. N/A]
Selection of station address. Every station connected to the same DeviceNet network must have an
unambiguous address.
10-05 Readout Transmit Error Counter
Range:
Function:
0 N/A*
[0 - 255 N/A]
View the number of CAN control transmission errors since the last power-up.
10-06 Readout Receive Error Counter
Range:
Function:
0 N/A*
[0 - 255 N/A]
View the number of CAN control receipt errors since the last power-up.
10-07 Readout Bus Off Counter
Range:
Function:
0 N/A*
[0 - 255 N/A]
View the number of Bus Off events since the last power-up.