9-63 Actual Baud Rate
Option:
Function:
This parameter displays the actual Profibus baud rate. The Profibus Master automatically sets the
baud rate.
[0]
9,6 kbit/s
[1]
19,2 kbit/s
[2]
93,75 kbit/s
[3]
187,5 kbit/s
[4]
500 kbit/s
[6]
1500 kbit/s
[7]
3000 kbit/s
[8]
6000 kbit/s
[9]
12000 kbit/s
[10]
31,25 kbit/s
[11]
45,45 kbit/s
[255] *
No baudrate found
9-65 Profile Number
Range:
Function:
0 N/A*
[0 - 0 N/A]
This parameter contains the profile identification. Byte 1 contains the profile number and byte 2 the
version number of the profile.
NB!
This parameter is not visible via LCP.
9-70 Programming Set-up
Option:
Function:
Select the set-up to be edited.
[0]
Factory setup
Uses default data. This option can be used as a data source to return the other set-ups to a known
state.
[1]
Set-up 1
Edits Set-up 1.
[2]
Set-up 2
Edits Set-up 2.
[3]
Set-up 3
Edits Set-up 3.
[4]
Set-up 4
Edits Set-up 4.
[9] *
Active Set-up
Follows the active set-up selected in par.0-10
This parameter is unique to LCP and fieldbuses. See also par.0-11
.