[161]
Running reverse
Output is high when the frequency converter is running counter clockwise (the logical product of
the status bits ‘running’ AND ‘reverse’).
[165]
Local ref active
Output is high when par.3-13
= [0]
Linked to hand auto
at the same time as the LCP is in Hand mode.
[166]
Remote ref active
Output is high when par.3-13
= Remote
[1] or
Linked to hand/auto
[0] while the
LCP is in [Auto] mode.
[167]
Start command act.
Output is high when there is an active Start command (i.e. via digital input bus connection or [Hand]
or [Auto]), and no Stop or Start command is active.
[168]
Hand mode
Output is high when the frequency converter is in Hand mode (as indicated by the LED light above
[Hand]).
[169]
Auto mode
Output is high when the frequency converter is in Hand on mode (as indicated by the LED light
above [Auto]).
[180]
Clock Fault
[181]
Prev. Maintenance
[190]
No-Flow
[191]
Dry Pump
[192]
End Of Curve
[193]
Sleep Mode
[194]
Broken Belt
[195]
Bypass Valve Control
[196]
Fire Mode
[197]
Fire Mode was Act.
[198]
Drive Bypass
[200]
Full capacity
[201]
Pump 1 running
[202]
Pump 2 running
[203]
Pump 3 running
5-33 Term X30/7 Digi Out (MCB 101)
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB 101 is mounted in the frequency converter.
[1]
Control ready
The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for operation and applies a supply signal on the control board.
[3]
Drive rdy/rem ctrl
The frequency converter is ready for operation and is in Auto mode.
[4]
Standby / no warning
Ready for operation. No start or stop command is been given (start/disable). There are no warnings.
[5]
Running
Motor is running.
[6]
Running / no warning
Output speed is higher than the speed set in par.1-81
Min Speed for Function at Stop [RPM]
motor is running and there are no warnings.
[8]
Run on ref/no warn
Motor runs at reference speed.
[9]
Alarm
An alarm activates the output. There are no warnings.
[10]
Alarm or warning
An alarm or a warning activates the output.
[11]
At torque limit
The torque limit set in par. 4-16
Torque Limit Motor Mode
or par. 1-17 has been exceeded.
[12]
Out of current range
The motor current is outside the range set in par. 4-18
Current Limit
.
[13]
Below current, low
Motor current is lower than set in par. 4-50
Warning Current Low
.
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
75