[70]
Logic rule 0
See par. group LC-4#. If Logic Rule 0 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[71]
Logic rule 1
See par. group LC-4#. If Logic Rule 1 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[72]
Logic rule 2
See par. group LC-4#. If Logic Rule 2 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[73]
Logic rule 3
See par. group LC-4#. If Logic Rule 3 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[74]
Logic rule 4
See par. group LC-4#. If Logic Rule 4 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[75]
Logic rule 5
See par. group LC-4#. If Logic Rule 5 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[84]
SL digital output E
[85]
SL digital output F
[160]
No alarm
Output is high when no alarm is present.
[161]
Running reverse
Output is high when the frequency converter is running counter clockwise (the logical product of
the status bits ‘running’ AND ‘reverse’).
[165]
Local ref active
Output is high when par.3-13
= [0]
Linked to hand auto
at the same time as the LCP is in Hand mode.
[166]
Remote ref active
Output is high when par.3-13
= Remote
[1] or
Linked to hand/auto
[0] while the
LCP is in [Auto] mode.
[167]
Start command act.
Output is high when there is an active Start command (i.e. via digital input bus connection or [Hand]
or [Auto]), and no Stop or Start command is active.
[168]
Hand mode
Output is high when the frequency converter is in Hand mode (as indicated by the LED light above
[Hand]).
[169]
Auto mode
Output is high when the frequency converter is in Auto mode (as indicated by the LED light above
[Auto]).
[180]
Clock Fault
[181]
Prev. Maintenance
[190]
No-Flow
[191]
Dry Pump
[192]
End Of Curve
[193]
Sleep Mode
[194]
Broken Belt
[195]
Bypass Valve Control
[200]
Full capacity
[201]
Pump 1 running
[202]
Pump 2 running
[203]
Pump 3 running
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
77