1-81 Min Speed for Function at Stop [RPM]
Range:
Function:
3. RPM*
[0 - 600 RPM]
Set the speed at which to activate par.1-80
1-82 Min Speed for Function at Stop [Hz]
Range:
Function:
0.1 Hz*
[0.0 - 20.0 Hz]
Set the output frequency at which to activate par.1-80
2.3.9 1-9* Motor Temperature
Parameters for setting the temperature protection features for the motor.
1-90 Motor Thermal Protection
Option:
Function:
The frequency converter determines the motor temperature for motor protection in two different
ways:
•
Via a thermistor sensor connected to one of the analog or digital inputs (par.1-93
•
Via calculation (ETR = Electronic Thermal Relay) of the thermal load, based on the actual
load and time. The calculated thermal load is compared with the rated motor current
I
M,N
and the rated motor frequency f
M,N
. The calculations estimate the need for a lower
load at lower speed due to less cooling from the fan incorporated in the motor.
[0]
No protection
If the motor is continuously overloaded and no warning or trip of frequency converter is wanted.
[1]
Thermistor warning
Activates a warning when the connected thermistor in the motor reacts in the event of motor over-
temperature.
[2]
Thermistor trip
Stops (trips) the frequency converter when the connected thermistor in the motor reacts in the
event of motor over-temperature.
[3]
ETR warning 1
[4] *
ETR trip 1
[5]
ETR warning 2
[6]
ETR trip 2
[7]
ETR warning 3
[8]
ETR trip 3
[9]
ETR warning 4
[10]
ETR trip 4
ETR (Electronic Thermal Relay) functions 1-4 will calculate the load when set-up where they were selected is active. For example ETR-3 starts calculating
when set-up 3 is selected. For the North American market: The ETR functions provide class 20 motor overload protection in accordance with NEC.
2 Parameter Description
VLT
®
AQUA Drive Programming Guide
44
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
2