29-01 Pipe Fill Speed [RPM]
Range:
Function:
Speed Low
Limit*
[Speed Low Limit - Speed High Lim-
it]
Set the filling speed for filling horizontal pipe systems. The speed can be selected in Hz or RPM
depending on the choices made in par. 4-11 / par. 4-13 (RPM) or in par. 4-12 / par. 4-14 (Hz).
29-02 Pipe Fill Speed [Hz]
Range:
Function:
Motor
Speed Low
Limit*
[Speed Low Limit - Speed High Lim-
it]
Set the filling speed for filling horizontal pipe systems. The speed can be selected in Hz or RPM
depending on the choices made in par. 4-11 / par. 4-13 (RPM) or in par. 4-12 / par. 4-14 (Hz).
29-03 Pipe Fill Time
Range:
Function:
0 s*
[0 - 3600 s]
Set the specified time for pipe filling of horizontal pipe systems.
29-04 Pipe Fill Rate
Range:
Function:
0.001 units/
s*
[0.001 – 999999.999 units/s]
Specifies the filling rate in units/second using the PI controller. Filling rate units are feedback units/
second. This function is used for filling-up vertical pipe systems but will be active when the filling-
time has expired, no matter what , until the pipe fill-set-point set in par. 29-05 is reached.
29-05 Filled Setpoint
Range:
Function:
0 s*
[0 – 999999,999 s]
Specifies the Filled Set-point at which the Pipe Fill Function will be disabled and the PID controller
will take control. This function can be used both for horizontal and vertical pipe systems.