Warnings are shown on display, programmed output or serial bus.
4-50 Warning Current Low
Range:
Function:
0.00 A*
[0.00 - par. 4-51 A]
Enter the I
LOW
value. When the motor current falls below this limit (I
LOW
), the display reads CURRENT
LOW. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02. Refer to the drawing in this section.
4-51 Warning Current High
Range:
Function:
par. 16-37
A*
[par. 4-50 - par. 16-37 A]
Enter the I
HIGH
value. When the motor current exceeds this limit (I
HIGH
), the display reads CURRENT
HIGH. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02. Refer to the drawing in this section.
4-52 Warning Speed Low
Range:
Function:
0 RPM*
[0 - par. 4-53 RPM]
Enter the n
LOW
value. When the motor speed falls below this limit (n
LOW
) the display reads SPEED
LOW. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02. Programme the lower signal limit of the motor speed, n
LOW
, within the
normal working range of the frequency converter. Refer to the drawing in this section.
4-53 Warning Speed High
Range:
Function:
par. 4-13
RPM*
[par. 4-52 - par. 4-13 RPM]
Enter the n
HIGH
value. When the motor speed exceeds this limit (n
HIGH
), the display reads SPEED
HIGH. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02. Programme the upper signal limit of the motor speed, n
HIGH
, within the
normal working range of the frequency converter. Refer to the drawing in this section.
NB!
Any changes in par.4-13
will reset the value in par.4-53
to the same value as set
.
If a different value is needed in par.4-53
, it must be set after programming of par.4-13
!
2 Parameter Description
VLT
®
AQUA Drive Programming Guide
60
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
2