12.10.49 Fault 11 - Output phase supervision, Subcode S4 - Additional closed loop output phase
fault during PM StartAngleID run
Cause
The measurement of current tells that there is no current in 1 motor phase.
It is possible to set different responses in the application for this fault. See parameter group Protections.
Troubleshooting
Do a check of the motor cable and the motor.
12.10.50 Fault 12 - Brake chopper supervision
Cause
•
There is no brake resistor.
•
The brake resistor is broken.
•
A defective brake chopper.
Troubleshooting
•
Do a check of the brake resistor and the cabling.
•
If they are in good condition, there is a fault in the resistor or the brake chopper. Ask instructions from the local distributor.
12.10.51 Fault 13 - AC drive undertemperature
Cause
Too low a temperature in the heat sink of the power unit or in the power board. The heat sink temperature is below -10 °C (14 °F).
Troubleshooting
Add an external heater near the AC drive.
12.10.52 Fault 14 - AC drive overtemperature, Subcode S1 - Overtemperature warning in unit,
board, or phases
Cause
Overheating detected in AC drive.
Heat sink temperature is over 90 °C (194 °F). Overtemperature alarm is issued when the heat sink temperature goes over 85 °C (185 °F).
In 525–690 V, FR6: Heat sink temperature is over 77 ºC (170.6 °F). Overtemperature alarm is issued when the heat sink temperature
goes over 72 ºC (161.6 °F).
Specifications
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 145
Danfoss A/S © 2019.11