Procedure
1. Connect the cables. See the correct tightening torques in
12.5 Tightening Torques of the Terminals
.
•
Connect the DC supply cables and the motor cables into the correct terminals.
•
Attach the grounding conductor of each cable to a grounding busbar in the cabinet.
2. Expose the shield of motor cables to make a 360° connection with the grounding clamp for cable shield.
1
2
e3
0b
h4
83
.1
0
1 Cable clamp
2 EMC grounding clamp
3. If the cables between the control unit and the ASIC board are not connected, connect each cable to its respective connector. See
.
4. Attach the cable cover. Use tightening torque 1.8 Nm.