Technical item or function
Technical data
Ambient conditions
Ambient operating temperature
–10°C (no frost)…+55°C
Storage temperature
-40 °C (-40 °F)...+70 °C (158 °F)
Relative humidity
0–95% RH, non-condensing, non-corrosive, no dripping water
Air quality:
•
chemical fumes
•
solid particles
Designed according to
•
IEC 60721-3-3, AC drive in operation, class 3C2
•
IEC 60721-3-3, AC drive in operation, class 3S2
Altitude
100% loadability (no derating) up to 1000 m.
Maximum elevation 2000 m (525–690 V AC) and 3000 m (380–500 V
AC)
Relay I/O: maximum 240 V: 3000 m; maximum 120 V: 4000 m
See Power derating as a function of installation altitude. See Chapter
4.4.
Vibration
Displacement amplitude 0.25 mm (peak) at 5…31 Hz
EN50178/EN60068-2-6
Max acceleration 1 G at 31…150 Hz
Shock
UPS Drop Test (for applicable UPS weights)
EN50178, EN60068-2-27
Storage and shipping: max 15 G, 11 ms (in package)
Heat loss
Ploss[kW] approx. Pmot[kW] × 0.02
Cooling air required
FI9: 750 m
3
/h
FI10: 1200 m
3
/h
FI12: 2400 m
3
/h
FI13: 3600 m
3
/h
FI14: 7200 m
3
/h
Unit protection rating
IP00/Open type standard size in the kW/HP range
EMC (at default set-
tings)
Immunity
IEC/EN 61800-3:2004+A1:2012, second environment
Noise level
Average noise level (cooling fan) in
dB(A)
FI9: 76
FI10: 74
FI12: 76
FI13: 81
FI14: 84
Safety standards
IEC/EN 61800-5-1, UL 508C, CSA C22.2 No.274
Specifications
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 129
Danfoss A/S © 2019.11