Technical item or function
Technical data
Functional safety
Hardware based ‘Safe Torque Off’
safety function to prevent the drive
from generating torque on the mo-
tor shaft.
STO safety function has been de-
signed for use in accordance with
the following standards
•
EN 61800-5-2 Safe Torque Off (STO) SIL3
•
EN ISO 13849-1 PL “e” Category 3
•
EN 62061 SILCL3
•
IEC 61508 SIL3
•
The function also corresponds to an uncontrolled stop in accord-
ance with stop category 0, EN 60204-1.
•
EN 954-1, Category 3
SS1 safety function is realized in
compliance with type C of the
drives safety standard EN61800-5-2
(Type C: “The PDS(SR) initiates the
motor deceleration and initiates
the STOfunction after an applica-
tion-specific time delay”).
SS1 safety function has been de-
signed for use in accordance with
the following standards:
•
EN 61800-5-2 Safe Stop 1 (SS1) SIL3
•
EN ISO 13849-1 PL "e" Category 3
•
EN 62061 SILCL3
•
IEC 61508 SIL3
•
The function also corresponds to a controlled stop in accordance
with stop category 1, EN60204-1.
ATEX thermistor input
94/9/EC, CE 0537 Ex 11 (2) GD
Approvals
CE, cULus, RCM, KC, EAC, UA. (See the nameplate of the drive for more
approvals.)
Marine approvals: LR, BV, DNV, GL, ABS, RMRS, CCS, KR.
Control connec-
tions
Analog input voltage
0…+10 V, R
i
= 200 kW, (–10 V…+10 V joystick control)
Resolution 0.1%, accuracy ±1%
Analog input current
0(4)…20 mA, R
i
= 250 W differential
Digital inputs (6)
Positive or negative logic; 18…30VDC
Auxiliary voltage
+24 V, ±15%, maximum 250 mA
Output reference voltage
+10 V, +3%, maximum load 10 mA
Analog output
0(4)…20 mA; RL maximum 500 W; Resolution 10 bit; Accuracy ±2%
Digital outputs
Open collector output, 50 mA/48 V
Relay outputs
2 programmable change-over relay outputs
Switching capacity: 24 V DC/8 A, 250 V AC/8 A, 125 V DC/0.4 A
Min.switching load: 5 V/10 mA
Specifications
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909
130 | Danfoss A/S © 2019.11