Operation malfunction
•
Defective component
Troubleshooting
•
Reset the fault and start the drive again.
•
If the fault shows again, ask instructions from the local distributor.
12.10.8 Fault 6 - Emergency stop
Cause
Stop signal has been given from the option board.
Troubleshooting
Do a check of the emergency stop circuit.
12.10.9 Fault 7 - Saturation trip
Cause
•
defective component
•
brake resistor short circuit or overload
Troubleshooting
This fault cannot be reset from the control panel.
•
Switch off the power.
•
DO NOT RESTART THE DRIVE or CONNECT THE POWER!
•
Ask instructions from the factory. If this fault shows at the same time with Fault 1, do a check of the motor cable and the motor.
12.10.10 Fault 8 - System fault, Subcode S1 - ASIC phase feedback
Cause
•
operation malfunction
•
defective component
Troubleshooting
•
Reset the fault and start the drive again.
•
If the fault shows again, ask instructions from the local distributor.
12.10.11 Fault 8 - System fault, Subcode S4 - ASIC trip
Cause
•
operation malfunction
•
defective component
Specifications
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 135